TOA Canada - Removing Capacitor from the PC-580RU

When using the PC-580RU as a talk-back speaker for some intercoms, it may be necessary to remove the DC blocking capacitor.

Some intercom systems are sensitive to the capacitive load that the PC-580RU presents to the circuit.

This capacitor is required for Fire Signaling use and removal of the capacitor will void UL-1480 compliance.

Simply cut the black wire and insert it in the negative terminal of the grey terminal block.

Note: If the capacitor is removed, the speaker will not comply with UL-1480.

MNS Design Worksheet

 

Note: removal of capacitor can result in nullification of Warranty. For detailed instructions and warranty concerns 
Contact our Technical Support Team @. 1-800-263-7639 x 320 or 
technicalsupport@toacanada.com